Database: MULTIPLE ITEMS
Item Tested |
Description |
Main Material |
Mass Fraction, Yi |
First Material to Ignite |
Total Weight (kg) |
Burning Characteristics |
Reference |
||
Flammable Mass (kg) |
HRRMAX (kW) |
ΔHC (MJ/kg) |
|||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had gypsum board walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test R1) | Cotton Felt |
X |
2109.4 |
Kim, Hyeong-Jin and David G. Lilley. "Heat Release Rates of Burning Items in Fires." AIAA 2000-0722. 38th Aerospace Sciences Meeting & Exhibit. Reno, NV. January 2000. | ||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Wood |
|||||||||
Gypsum Wallboard |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test R5) | Cotton Felt |
X |
6829.5 |
Kim, Hyeong-Jin and David G. Lilley. "Heat Release Rates of Burning Items in Fires." AIAA 2000-0722. 38th Aerospace Sciences Meeting & Exhibit. Reno, NV. January 2000. | ||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Wood |
|||||||||
Plywood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O1) | Polyurethane |
X |
53.7 |
1200 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Wood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O2) | Polyurethane |
X |
53.7 |
1100 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Wood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O3) | Polyurethane |
X |
53.7 |
700 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Gypsum Wallboard |
|||||||||
Wood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O4) | Polyurethane |
X |
53.7 |
1300 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Gypsum Wallboard |
|||||||||
Wood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O5) | Polyurethane |
X |
53.7 |
1300 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Plywood |
|||||||||
Wood |
|||||||||
Bed, Room | Bedroom setup including: a double bed, bedding, night table. Room had plywood walls. Ignition source was a wastebasket with 0.75 kg of trash. (Test O6) | Polyurethane |
X |
53.7 |
1500 |
Lee, B.T. "Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park Lodgining Bedroom Fire." NBSIR 85-2998. National Bureau of Standards, Gaithersburg, MD. February 1985 | |||
Cotton Felt |
|||||||||
Urethane Foam |
|||||||||
Cotton Fabric |
|||||||||
Plywood |
|||||||||
Wood |
|||||||||
Workstation (2 Panels) | Workstation consisted of 2 panels with a desk, office chair, monitor and commodities (paper reams). Test sponsored by GSA and performed at BFRL in 1991. Complete data is available at http://www.fire.nist.gov/fire/fires/work2/work2.html | Workstation |
1.00 |
X |
1746.2 |
National Institute of Standards and Technology. "Two Panel Workstation Fire." <http://www.fire.nist.gov/fire/fires/work2/work2.html> | |||
Workstation (3 Panels) | Workstation consisted of 3 panels with a desk, office chair, monitor and commodities (paper reams). Test sponsored by GSA and performed at BFRL in 1991. Complete data is available at http://www.fire.nist.gov/fire/fires/work3/work3.html | Workstation |
1.00 |
X |
6719.7 |
National Institute of Standards and Technology. "Three Panel Workstation Fire." <http://www.fire.nist.gov/fire/fires/work3/work3.html> | |||
Workstation, Laboratory | Laboratory workstation consisted of a steel laboratory bench with closed drawers and a stone bench top. Setup also included a shelving unit above the bench. Both the shelving unit and lab bench were loaded with numerous fuel items (i.e. paper, boxes, and | Steel |
50.8 |
2000 |
Walton, W.D. "Quick Response Sprinklers in Chemical Laboratories: Fire Test Results." US Department of Commerce. Maryland: 1989. | ||||
Wood |
|||||||||
Paper |
X |
||||||||
Workstation, Computer | Computer workstation consisting of a computer desk and a bookcase. Each were constructed with 5/8" thick particle board covered with aimulates wood, plastic laminate. The desk was loaded with 99 lb of paper materials and the bookcase was loaded with 160 lb of paper materials. (Test 101) | Paper |
X |
1420 |
Walton, WD and EK Budnick. "Quick Response Sprinklers in Office Configurations: Fire Test Results." NBSIR 88-3695. US Department of Commerce. Maryland: 1988. | ||||
Particleboard |
|||||||||
Workstation, Computer | Computer workstation consisting of a computer desk and a bookcase. Each were constructed with 5/8" thick particle board covered with aimulates wood, plastic laminate. The desk was loaded with 99 lb of paper materials and the bookcase was loaded with 160 lb of paper materials. (Test 102) | Paper |
X |
1830 |
Walton, WD and EK Budnick. "Quick Response Sprinklers in Office Configurations: Fire Test Results." NBSIR 88-3695. US Department of Commerce. Maryland: 1988. | ||||
Particleboard |